Construction· Measure twice, buy once
Estimate a building's design heat loss from walls, windows, roof and ventilation, in kW and BTU/h.
Formula
heat loss (W) = Σ U × A × ΔT (walls, windows, roof) + 0.33 × air changes per hour × volume × ΔT
Worked example
120 m² walls (U 0.35), 20 m² windows (U 2.0), 80 m² roof (U 0.25), 200 m³ at 0.5 ACH, ΔT 24 °C: about 3.24 kW (11,055 BTU/h).
Free to use with a link back. Nothing you type is shared.
Preparing citation…
Keep exploring
Find the air conditioner capacity in BTU per hour for a room, using the ENERGY STAR sizing chart and its adjustments.
Open calculatorEstimate what an appliance costs to run per day, month and year from its wattage, hours of use and your electricity price.
Open calculator