Find the smallest copper or aluminum AWG wire that carries the current (NEC 75 °C ampacity) within your voltage-drop limit.
Formula
smallest size with ampacity ≥ current and voltage drop ≤ limit; drop from the conductor's resistance over the round-trip length
Worked example
30 A at 240 V single-phase over 35 m with a 3% maximum drop, copper: 8 AWG (10 AWG carries 30 A but drops about 3.49%; 8 AWG drops 2.19%).